Since the use of condensing and evaporation units used in rooms, cabins or cooling processes requiring energy from the electrical network has increased rapidly in recent years, it was considered necessary to develop a standard to determine the energy efficiency of these equipment, to control their cooling capacities and to contribute to the protection of non-renewable natural resources by reducing the energy consumption of this concept by integrating these units into a cooling system.

The standard “NOM-012-ENER Energy efficiency of condensing and evaporating units for refrigeration - Limits, test methods and labeling”, published under the Official Mexican Standard (NOM), describes the energy efficiency requirements that condensing and evaporating units must meet, as well as test methods to verify compliance, labeling and the procedure for evaluating the conformity of products.
The scope of this standard includes:
The following are outside the scope of this standard:
Condensing and evaporation units are classified differently based on their cooling applications and usage in cooling systems:
Condensing units within the scope of this standard must comply with the gross cooling capacities specified in the table entitled “Minimum standardized energy efficiency factor level to be met according to the power of the condensing unit ” and with the standardized energy efficiency factor values in accordance with the test method described in this standard.
Likewise, the cooling capacity and electrical power consumption values of these units must comply with the values declared by the manufacturer with a tolerance of plus/minus 5,0 percent compared to the value stated on the label.
Evaporator units within the scope of this standard must comply with the cooling capacities specified in the table titled “Minimum level of standardized energy efficiency factor on evaporator units for cooling” and the standardized energy efficiency factor values in accordance with the test method described in this standard.
Likewise, the cooling capacity and electrical power consumption values of these units must comply with the values declared by the manufacturer with a tolerance of plus/minus 5,0 percent compared to the value stated on the label.
To determine the cooling capacity and standardized energy efficiency factor of equipment covered by this standard, the following tests must be performed:
The tables given in the standard specify the standard evaluation conditions under which the steady state performance tests of the condensing and evaporating units, respectively, should be performed.
The condensing units being tested should be connected to a calorimeter capable of providing and controlling the gross cooling capacity stated on the manufacturer's label. An evaporator meeting the steady-state conditions given in the table may be used for testing.
To measure the refrigerant mass flow rate, a liquid flow mass flow meter is installed at the outlet of the condensing unit. It should be ensured that there is a single-phase refrigerant flow from the liquid cooling mass flow meter.
Our organization, which has been trying to support businesses from every sector with its wide range of testing, measurement, analysis and evaluation studies for years, has a strong staff that closely follows the developments in the world in the field of science and technology and constantly improves itself. In this context, testing services are also provided to businesses in accordance with the standard “NOM-012-ENER Energy efficiency of condenser and evaporator units for cooling - Limits, test methods and labeling”.