EN 13880-2 Hot Applied Sealants - Part 2: Test Method for Determination of Cone Penetration at 25 Degrees

EN 13880-2 Hot Applied Sealants - Part 2: Test Method for Determination of Cone Penetration at 25 Degrees

A European standard “EN 13880-2 Hot-applied grouts - Part 2: Test method for determination of cone penetration at 25 degrees” describes a method for determining the cone penetration of hot-applied grouts using a standard penetrometer equipped with a suitable penetration cone. Initial and fuel immersion penetration values ​​are recorded using this test method as required in the standard “prEN 14188-1 Grouts and sealants - Part 1: Requirements for hot-applied sealants”.

EN 13880-2 Hot Applied Sealants - Part 2: Test Method for Determination of Cone Penetration at 25 Degrees

For the purposes of this standard, the cone penetration value expresses the depth to which a standard cone penetrates the test specimen under defined conditions of mass, time and temperature.

When performing the test, in principle, a portion of the sample is poured into two metal containers and used with a transfer cup to provide test samples that are conditioned by immersion in a water bath cooled by air and at a constant temperature. After the conditioning period, the transfer cup containing the test samples is removed from the water bath and placed on the penetration apparatus stand. The cone penetration test is immediately performed on the test samples.

The main equipment used in these tests includes:

  • Penetrometer: Must comply with EN 1426 standard. To facilitate leveling, the penetrometer is equipped with leveling screws. Automatically controlled equipment can also be used in these tests. Such equipment needs regular calibration for correct penetration time.
  • Penetration cone: It is a cone made of brass and complies with the dimensions given in the figure. The outer surface and tip of the cone should have a smooth polished surface. The total moving mass of the cone and connections should be 150,0 plus/minus 0,1 g.
  • Water bath: A water bath with a water capacity of at least 10 l, a perforated shelf at least 50 mm from the bottom of the bath and capable of holding the test samples at the required test temperature of 25,0 degrees plus/minus 0,3 degrees.
  • Transfer cup: Consisting of a cylindrical glass or metal cup with a flat bottom, the transfer cup is provided to provide a firm bearing and prevent rocking when placed on the penetration apparatus stand. The cup should have a minimum inside diameter of 90 mm and a minimum depth of 56 mm above the base bearing.
  • Metal containers: Two flat-bottomed metal containers of cylindrical shape and a nominal capacity of approximately 100 g in which the test specimens are tested. The internal dimensions of the containers shall be 56 mm plus/minus 5 mm in diameter and 35 mm plus/minus 2 mm deep. A marking shall be made at a depth of 30 mm to facilitate pouring the correct amount of material.

The test samples are prepared according to prEN 13880-6. The test sample is poured, taking care to avoid any contamination. The actual temperature is recorded at the end of the pouring process. Immediately after filling, each metal container and its contents are loosely covered with a beaker of appropriate size to protect against dust and to help eliminate air bubbles. The test samples are allowed to cool in air at 23°C plus/minus 2°C (1,75 hours plus/minus 0,25 hours). The test samples are placed in the water bath with the transfer container and allowed to remain immersed for a further 1,75 hours plus/minus 0,25 hours.

The test conditions shall be as follows: temperature 25,0 degrees plus/minus 0,3 degrees, applied load 150,0 plus/minus 0,1 g, and loading time 5,0 seconds plus/minus 0,1 seconds.

When supported on the rack during the test, the test specimen is immersed in water to a depth of at least 50 mm. Distilled or deionized water should be used in the bath. After the immersion period in the water bath, the test specimens are placed from the water bath into a transfer vessel filled with water to a depth sufficient to completely cover the metal vessel. The transfer vessel containing the test specimen is removed from the water bath, placed on the stand of the penetration apparatus and tested within 1 minute.

The penetration cone, which should be at a temperature of approximately 25 degrees, is adjusted so that its tip is in contact with the surface of the test specimen. The cone is released for 5,0 seconds plus/minus 0,1 seconds, fixed and the distance penetrated is measured. Three determinations are made at points on the surface of the test specimen at least 16 mm from the sides of the metal container and from each other. Between determinations, the test specimen is returned and the tip of the cone is carefully wiped with a clean cloth and the container is transferred to the water bath. If the result of any determination differs by more than 0,5 mm from the average of the three determinations, the results are discarded and the test is repeated on a new test specimen.

Among the numerous tests, measurements, analyses and evaluation studies that our organization has carried out for businesses in various sectors, it also provides testing services defined in the standard “EN 13880-2 Hot applied joint sealants - Part 2: Test method for determining cone penetration at 25 degrees” with its trained and expert staff and advanced technological equipment.